FS-8700-88 Envirotronics SystemsPlus Page 40 of 49
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: supp[email protected]m
4.4.98. Map Descriptor Example 94 - edit read analog type
// Client Side Mao Descriptors
Map Descriptor
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function,
Node_Name, SysPlus_Cmd, Store_Data_Array_Name, Store_Data_Array_Offset, Length
Ed_Rd_Ana_Type, Rd_Triggers, 10, art, SYSPLUS_01, Ed_Rd_Ana_Type, Ed_Rd_Ana_Type, 0, 1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.
The retrieved data is stored as follows:
Offset from Store_Data_Array_Offset
Description
0 Analog type
4.4.99. Map Descriptor Example 95 - edit read engineering min.
// Client Side Mao Descriptors
Map Descriptor
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function,
Node_Name, SysPlus_Cmd, Store_Data_Array_Name, Store_Data_Array_Offset, Length
Ed_Rd_Eng_Min, Rd_Triggers, 11, art, SYSPLUS_01, Ed_Rd_Eng_Min, Ed_Rd_Eng_Min, 0, 1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.
The retrieved data is stored as follows:
Offset from Store_Data_Array_Offset
Description
0 Min engineering value
4.4.100. Map Descriptor Example 96 - edit read engineering max.
// Client Side Mao Descriptors
Map Descriptor
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function,
Node_Name, SysPlus_Cmd, Store_Data_Array_Name, Store_Data_Array_Offset, Length
Ed_Rd_Eng_Max, Rd_Triggers, 12, art, SYSPLUS_01, Ed_Rd_Eng_Max, Ed_Rd_Eng_Max, 0, 1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.
The retrieved data is stored as follows:
Offset from Store_Data_Array_Offset
Description
0 Max engineering value
Przeglądanie stron 39